GDL型立式多級管道離心泵是我司在國外優(yōu)秀泵型之基礎(chǔ)上結(jié)合用戶的使用要求及消防有關(guān)標(biāo)準(zhǔn),并根據(jù)JB/TQ6435-92標(biāo)準(zhǔn)設(shè)計(jì)制造的新一代產(chǎn)品。本司產(chǎn)品全部采用計(jì)算機(jī)設(shè)計(jì)和優(yōu)化處理,公司擁有雄厚的技術(shù)力量、豐富的生產(chǎn)經(jīng)驗(yàn)和完善的檢測手段,從而保證產(chǎn)品質(zhì)量的穩(wěn)定可靠。
GDL型立式多級管道離心泵吸入、排出口位于同一直線上。轉(zhuǎn)子部件由軸、葉輪、葉輪擋套、軸套等零件組成,進(jìn)水段、中段、出水段用拉緊螺栓聯(lián)結(jié)。軸封采用機(jī)械密封,用平衡室的壓力水進(jìn)行潤滑和冷卻。是各大行業(yè)冷熱水或物理化學(xué)性質(zhì)類似于水等液體輸送的較佳泵型。
廣泛應(yīng)用于高壓運(yùn)行系統(tǒng)中冷熱清水的循環(huán)和增壓、高層建筑多臺泵并聯(lián)供水、消防、鍋爐給水和冷卻水系統(tǒng)及各種沖洗液的輸送等。
型號 | 流量m3/h | 揚(yáng)程m | 吸程m | 電機(jī)功率kw |
25GDL2-12×3 | 2 | 36 | 7.5 | 1.1 |
25GDL2-12×4 | 48 | 1.1 | ||
25GDL2-12×5 | 60 | 1.5 | ||
25GDL2-12×6 | 72 | 1.5 | ||
25GDL2-12×7 | 84 | 2.2 | ||
25GDL2-12×8 | 96 | 2.2 | ||
25GDL2-12×9 | 108 | 2.2 | ||
25GDL2-12×10 | 120 | 3 | ||
25GDL2-12×11 | 132 | 3 | ||
25GDL2-12×12 | 144 | 3 | ||
25GDL4-11×3 | 4 | 33 | 1.1 | |
25GDL4-11×4 | 44 | 1.5 | ||
25GDL4-11×5 | 55 | 2.2 | ||
25GDL4-11×6 | 66 | 2.2 | ||
25GDL4-11×7 | 77 | 3 | ||
25GDL4-11×8 | 88 | 3 | ||
25GDL4-11×9 | 99 | 3 | ||
25GDL4-11×10 | 110 | 4 | ||
25GDL4-11×11 | 121 | 4 | ||
25GDL4-11×12 | 132 | 4 | ||
25GDL4-11×13 | 143 | 4 | ||
40GDL6-12×3 | 6 | 36 | 1.5 | |
40GDL6-12×4 | 48 | 2.2 | ||
40GDL6-12×5 | 60 | 2.2 | ||
40GDL6-12×6 | 72 | 3 | ||
40GDL6-12×7 | 84 | 3 | ||
40GDL6-12×8 | 96 | 4 | ||
40GDL6-12×9 | 108 | 4 | ||
40GDL6-12×10 | 120 | 4 | ||
40GDL6-12×11 | 132 | 5.5 | ||
40GDL6-12×12 | 144 | 5.5 | ||
50GDL12-15×2 | 12 | 30 | 7 | 2.2 |
50GDL12-15×3 | 45 | 3 | ||
50GDL12-15×4 | 60 | 4 | ||
50GDL12-15×5 | 75 | 5.5 | ||
50GDL12-15×6 | 90 | 5.5 | ||
50GDL12-15×7 | 105 | 7.5 | ||
50GDL12-15×8 | 120 | 75 | ||
50GDL12-15×9 | 135 | 11 | ||
50GDL12-15×10 | 150 | 11 | ||
50GDL18-15×3 | 18 | 45 | 4 | |
50GDL18-15×4 | 60 | 5.5 | ||
50GDL18-15×5 | 75 | 7.5 | ||
50GDL18-15×6 | 90 | 7.5 | ||
50GDL18-15×7 | 105 | 11 | ||
50GDL18-15×8 | 120 | 11 | ||
50GDL18-15×9 | 135 | 15 | ||
50GDL18-15×10 | 150 | 15 | ||
65GDL24-12×2 | 24 | 24 | 6 | 3 |
65GDL24-12×3 | 36 | 4 | ||
65GDL24-12×4 | 48 | 5.5 | ||
65GDL24-12×5 | 60 | 7.5 | ||
65GDL24-12×6 | 72 | 7.5 | ||
6S5GDL24-12×7 | 84 | 11 | ||
65GDL24-12×8 | 96 | 11 | ||
65GDL24-12×9 | 108 | 15 | ||
65GDL24-12×10 | 120 | 15 | ||
80GDL36-12×2 | 36 | 24 | 5.5 | 4 |
80GDL36-12×3 | 36 | 5.5 | ||
80GDL36-12×4 | 48 | 7.5 | ||
80GDL36-12×5 | 60 | 11 | ||
80GDL36-12×6 | 72 | 11 | ||
80GDL36-12×7 | 84 | 15 | ||
80GDL36-12×8 | 96 | 15 | ||
80GDL36-12×9 | 108 | 18.5 | ||
80GDL36-12×10 | 120 | 18.5 | ||
80GDL54-14×2 | 54 | 28 | 5 | 7.5 |
80GDL54-14×3 | 42 | 11 | ||
80GDL54-14×4 | 56 | 15 | ||
80GDL54-14×5 | 70 | 18.5 | ||
80GDL54-14×6 | 84 | 18.5 | ||
80GDL54-14×7 | 98 | 22 | ||
100GDL72-14×2 | 72 | 28 | 4.5 | 11 |
100GDL72-14×3 | 42 | >15 | ||
100GDL72-14×4 | 56 | 18.5 | ||
100GDL72-14×5 | 70 | 22 | ||
100GDL72-14×6 | 84 | 3>0 | ||
100GDL72-14×7 | 98 | 30 |
故障現(xiàn)象 | 可能產(chǎn)生的原因 | 排除方法 |
1、水泵不出水 | 進(jìn)水口閥門未打開,進(jìn)出管路阻塞,葉輪流道阻塞 電機(jī)運(yùn)行方向不對,電機(jī)缺相轉(zhuǎn)速很慢 吸入管漏氣 泵沒灌滿液體,泵腔內(nèi)有空氣 進(jìn)口供水不足,吸程過高,底閥漏水 管路阻力過大,泵選型不當(dāng) |
檢查,去除阻塞物 調(diào)整電機(jī)轉(zhuǎn)向,緊固電機(jī)接線 擰緊各密封面,排除空氣 打開泵上蓋或打開排氣閥,排盡空氣 停機(jī)檢查、調(diào)整 減少管路彎道,重新選泵 |
2、水泵流量不足 | 先按1原因檢查 管道、泵流道或葉輪部分阻塞,水垢沉積…… 電壓偏低 葉輪磨損 |
先按1排除 去除阻塞物,重新調(diào)整閥門開度 穩(wěn)壓 更換葉輪 |
3、功率過大 | 超過額定流量使用 吸程過高 泵軸承磨損 |
調(diào)節(jié)流量,關(guān)小出口閥門 降低 更換軸承 |
4、雜音振動 | 管路支撐不穩(wěn) 液體混有氣體 產(chǎn)生汽蝕 軸承損壞 電機(jī)超載運(yùn)行 |
穩(wěn)固管路 提高吸入壓力,排氣 降低真空度 更換軸承 調(diào)整按5 |
5、電機(jī)發(fā)熱 | 流量過大,超載運(yùn)行 局部摩擦 電機(jī)軸承損壞 電壓不足 |
關(guān)小出口閥門 檢查排除 更換軸承 穩(wěn)壓 |
6、水泵漏水 | 機(jī)械密封磨損 泵體有砂孔或破裂 密封面不平整 安裝螺栓松懈 |
更換 焊補(bǔ)或更換 修整 緊固 |
版權(quán)所有 ? 上海邁科泵業(yè)制造有限公司 銷售電話:021 - 56625995,36339855 E-mail: maike168@126.com 滬ICP備09048599號-1